94
Coding in the delivered condition
Possible change
Service interval in months
23:0
No time set for burner service in-
terval
23:1
to
23:24
Interval adjustable from 1 to
24 months
Service status
24:0
"Service"
not shown on the dis-
play
24:1
"Service"
shown on the display.
The address is set automatically and
must be reset manually after a serv-
ice.
Filling/venting
2F:0
Venting program/fill program disa-
bled
2F:1
Venting program enabled
2F:2
Fill program enabled
"DHW"
Select
"DHW"
(see page 92).
Coding
Coding in the delivered condition
Possible change
Enable DHW circulation pump
73:0
DHW circulation pump: "ON" ac-
cording to time program
73:1
to
73:6
During time program
"ON" for 5 min once an hour up to
"ON" for 5 min six times an hour
73:7
Permanently "ON"
"Heating circuit ..."
Select
"Heating circuit ..."
Coding
Coding in the delivered condition
Possible change
Economy function, outside temperature
A5:5
With heating circuit pump logic
function (economy control): Heat-
ing circuit pump "OFF" when the
outside temperature (OT) is 1 K
higher than the set room tempera-
ture (RT
set
)
OT
>
RT
set
+ 1 K
A5:0
Without heating circuit pump logic
function
A5:1
to
A5:15
With heating circuit pump logic func-
tion: heating circuit pump "OFF"; see
following table
Parameter address A5:...
With heating circuit pump logic function: Heating circuit pump "OFF"
1
OT
>
RT
set
+ 5 K
2
OT
>
RT
set
+ 4 K
3
OT
>
RT
set
+ 3 K
4
OT
>
RT
set
+ 2 K
5
OT
>
RT
set
+ 1 K
6
OT
>
RT
set
Codes
Coding level 1
(cont.)
5775 636 GB
Codes
Summary of Contents for C3TB
Page 136: ...136 Troubleshooting Repairs gas condensing module cont 5775 636 GB Diagnosis ...
Page 143: ...143 Parts lists Heat cell assembly 5775 636 GB Components ...
Page 160: ...160 Parts not shown 0009 PCB IU100 B30 Parts lists Fuel cell assembly 5775 636 GB Components ...
Page 161: ...161 Parts lists Fuel cell assembly cont 5775 636 GB Components ...
Page 187: ...187 5775 636 GB ...