114
2.
On programming unit
B
, select the required dis-
play (
81
to
85
) under
ITEM
using / .
In displays
81
to
85
, the set value and the
response time are shown alternately.
For an explanation of the displays, see the follow-
ing table:
ITEM
Meaning
Set value
Response time
81
Min. voltage
184 V
200 s
82
Max. voltage
253 V
600 s
83
Max. voltage
264.5 V
200 ms
84
Min. frequency
47.5 Hz
200 ms
85
Max. frequency
51.5 Hz
200 ms
Resetting fuel cell module data
The following statistical data from the fuel cell module
can be reset:
■
Power generated
■
CO2 reduction
■
Gas consumption history
Extended menu
1.
2.
"Service"
3.
"Service functions"
4.
"Reset fuel cell data"
Diagnosis and service scans
Fuel cell module
(cont.)