175
Example using the settings in the delivered condition
10
0
20
30
30
40
50
60
6
7
8
9
Boiler
water
temperature/
set flow temperature
in
°C
Time
A
B
C
D
Fig. 138
A
Start of operation with standard room temperature
B
Set boiler water or flow temperature in accordance
with the selected heating curve
C
Set boiler water or flow temperature in accordance
with coding address "FA":
50 °C + 20 % = 60 °C
D
Duration of operation with raised set boiler water
or flow temperature in accordance with coding
address "Fb":
60 min
Assigning heating circuits to the remote control
The heating circuit assignment must be configured
when commissioning the Vitotrol.
Heating circuit
Vitotrol configuration
200-A/200-RF
300-A/300-RF
The remote control affects the heating circuit without mixer A1.
H 1
HC 1
The remote control affects the heating circuit with mixer M2.
H 2
HC 2
The remote control affects the heating circuit with mixer M3.
H 3
HC 3
■
One heating circuit can be assigned to the Vitotrol
200A/200 RF.
■
Up to three heating circuits can be assigned to the
Vitotrol 300A/300 RF.
■
Up to 2 remote control units can be connected to the
control unit.
■
If the assignment of a heating circuit is later cancel-
led, reset coding address A0 for this heating circuit to
0 (fault message bC, bd, bE).
Function description
Control functions
(cont.)
5775 636 GB
Functions
Summary of Contents for C3TB
Page 136: ...136 Troubleshooting Repairs gas condensing module cont 5775 636 GB Diagnosis ...
Page 143: ...143 Parts lists Heat cell assembly 5775 636 GB Components ...
Page 160: ...160 Parts not shown 0009 PCB IU100 B30 Parts lists Fuel cell assembly 5775 636 GB Components ...
Page 161: ...161 Parts lists Fuel cell assembly cont 5775 636 GB Components ...
Page 187: ...187 5775 636 GB ...