104
Coding
Coding in the delivered condition
Possible change
56:0
Set DHW temperature adjustable
from 50 to 60 °C
56:1
Set DHW temperature adjustable
from 50 to 60 °C
Note
Maximum value subject to boiler
coding card.
Observe the maximum permissible
DHW temperature.
57:0
Never adjust
58:0
Without auxiliary function for DHW
heating
58:50
to
58:60
Input of a second set DHW tempera-
ture, adjustable from 50 to 60 °C.
Observe coding address "56" and
"63" in this group.
59:0
Cylinder heating:
Start point -2.5 K
Stop point +2.5 K
59:1
to
59:10
Start point adjustable from 1 to 10 K
below set value
5A:1
Never adjust
5E:0
Never adjust
5F:0
Never adjust
60:20
During DHW heating, the boiler
water temperature is set up to 20 K
higher than the set DHW tempera-
ture.
60:5
to
60:25
The differential between the boiler
water temperature and the set DHW
temperature is adjustable from 5 to
25 K
62:2
Circulation pump with 2 min run-on
time after cylinder heating
62:0
No circulation pump run-on
62:1
to
62:15
Run-on time adjustable from 1 to
15 min
65:...
Never adjust
Information on type of diverter
valve, defaulted by the coding card
6C:100
Set speed of internal circulation
pump for DHW heating 100 %
6C:0
to
6C:100
Set speed adjustable from 0 to
100 %
6F:...
Max. heating output for DHW heat-
ing in %, defaulted by the coding
card
6F:0
to
6F:100
Max. heating output for DHW heat-
ing adjustable from min. heating out-
put to 100 %
71:0
DHW circulation pump: "ON" ac-
cording to time program
71:1
"OFF" during DHW heating to set
value 1
71:2
"ON" during DHW heating to set val-
ue 1
72:0
DHW circulation pump: "ON" ac-
cording to time program
72:1
"OFF" during DHW heating to set
value 2
72:2
"ON" during DHW heating to set val-
ue 2
73:0
DHW circulation pump: "ON" ac-
cording to time program
73:1
to
73:6
During time program
"ON" for 5 min once an hour up to
"ON" for 5 min six times an hour
73:7
Permanently "ON"
Codes
Coding level 2
(cont.)
5775 636 GB
Codes
Summary of Contents for C3TB
Page 136: ...136 Troubleshooting Repairs gas condensing module cont 5775 636 GB Diagnosis ...
Page 143: ...143 Parts lists Heat cell assembly 5775 636 GB Components ...
Page 160: ...160 Parts not shown 0009 PCB IU100 B30 Parts lists Fuel cell assembly 5775 636 GB Components ...
Page 161: ...161 Parts lists Fuel cell assembly cont 5775 636 GB Components ...
Page 187: ...187 5775 636 GB ...