119
Fault code dis-
played
System characteristics
Cause
Measures
CF
Control mode
No communication via LON
Communication error,
LON communication mod-
ule
Check LON communication mod-
ule and replace if required.
If no LON communication module
is installed, set code "76:0" in
"General"
group.
d6
Control mode
Input DE1 at EA1 exten-
sion reports a fault.
Remedy fault at appliance con-
cerned.
d7
Control mode
Input DE2 at EA1 exten-
sion reports a fault.
Remedy fault at appliance con-
cerned.
d8
Control mode
Input DE3 at EA1 exten-
sion reports a fault.
Remedy fault at appliance con-
cerned.
dA
Control mode without room
influence
Short circuit, room tem-
perature sensor, heating
circuit 1 (without mixer)
Check room temperature sensor,
heating circuit 1.
db
Control mode without room
influence
Short circuit, room tem-
perature sensor, heating
circuit 2 (with mixer)
Check room temperature sensor,
heating circuit 2.
dC
Control mode without room
influence
Short circuit, room tem-
perature sensor, heating
circuit 3 (with mixer)
Check room temperature sensor,
heating circuit 3.
dd
Control mode without room
influence
Lead break, room temper-
ature sensor, heating cir-
cuit 1 (without mixer)
Check room temperature sensor,
heating circuit 1 and remote control
configuration (see page 175).
dE
Control mode without room
influence
Lead break, room temper-
ature sensor, heating cir-
cuit 2 (with mixer)
Check room temperature sensor,
heating circuit 2 and remote control
configuration (see page 175).
dF
Control mode without room
influence
Lead break, room temper-
ature sensor, heating cir-
cuit 3 (with mixer)
Check room temperature sensor,
heating circuit 3 and remote control
configuration (see page 175).
E0
Control mode
External LON subscriber
error
Check connections and LON sub-
scribers.
E1
Burner in a fault state
Ionisation current too high
during calibration
Check gap between ionisation
electrode and burner gauze as-
sembly (see page 78).
In open flue operation, prevent
high levels of dust in the combus-
tion air.
Press reset
R
.
E2
Burner in a fault state
Heat transfer too low dur-
ing calibration.
Ensure adequate heat transfer.
Press reset
R
.
E3
Burner in a fault state
Heat transfer too low dur-
ing calibration.
Temperature limiter has
shut down.
Ensure adequate heat transfer.
Press reset
R
.
E4
Burner blocked
24 V power supply fault
Replace control unit.
E5
Burner blocked
Flame amplifier fault
Replace control unit.
E6
Burner blocked
System pressure too low
Top up with water.
Troubleshooting
Fault codes for gas condensing module
(cont.)
5775 636 GB
Diagnosis
Summary of Contents for C3TB
Page 136: ...136 Troubleshooting Repairs gas condensing module cont 5775 636 GB Diagnosis ...
Page 143: ...143 Parts lists Heat cell assembly 5775 636 GB Components ...
Page 160: ...160 Parts not shown 0009 PCB IU100 B30 Parts lists Fuel cell assembly 5775 636 GB Components ...
Page 161: ...161 Parts lists Fuel cell assembly cont 5775 636 GB Components ...
Page 187: ...187 5775 636 GB ...