Checking the fuse/MCB
F1
A
Fig. 110
1.
Switch off the power supply.
2.
Release the side closures and pivot the control unit
down.
3.
Remove cover
A
.
4.
Check fuse F1 (see connection and wiring dia-
gram).
Mixer extension kit
Checking the setting of rotary selector S1
The rotary selector on the PCB of the extension kit
defines the assignment to the relevant heating circuit.
Heating circuit
Rotary selector S1
setting
Heating circuit with mixer M2
(heating circuit 2)
2
2 3
4
5
6
1
0
9
8
7
Heating circuit with mixer M3
(heating circuit 3)
4
4
2 3
5
6
1
0
9
8
7
Checking the rotational direction of the mixer
motor
After being switched on, the boiler implements a self-
test. During this, the mixer is opened and closed again.
Note
The mixer motor can also be started via the actuator
test (see chapter "Checking outputs").
Observe the rotational direction of the mixer motor dur-
ing its self-test.
Then manually set the mixer back to "Open".
The flow temperature sensor must now capture a
higher temperature. If the temperature drops, either
the motor is turning in the wrong direction or the mixer
insert is incorrectly fitted.
Mixer installation instructions
Changing the rotational direction of the mixer motor (if required)
gS
BU
|
~
Fig. 111
1.
Remove the upper casing cover of the extension
kit.
Danger
An electric shock can be life-threatening.
Before opening the boiler, disconnect it from
the mains voltage, e.g. at the fuse or mains
isolator.
Troubleshooting
Repairs (gas condensing module)
(cont.)
5775 636 GB
Diagnosis
Summary of Contents for C3TB
Page 136: ...136 Troubleshooting Repairs gas condensing module cont 5775 636 GB Diagnosis ...
Page 143: ...143 Parts lists Heat cell assembly 5775 636 GB Components ...
Page 160: ...160 Parts not shown 0009 PCB IU100 B30 Parts lists Fuel cell assembly 5775 636 GB Components ...
Page 161: ...161 Parts lists Fuel cell assembly cont 5775 636 GB Components ...
Page 187: ...187 5775 636 GB ...