169
The duration of the changeover is set via coding
address F2 in the
"Heating circuit"
group.
Effect of external blocking function on the pumps
The effect on the internal circulation pump is selected
in coding address 3E in the
"General"
group.
The effect on the relevant heating circuit pump is
selected in coding address d6 in the
"Heating circuit"
group.
The effect on a circulation pump for cylinder heating is
selected in coding address 5E in the
"DHW"
group.
Effect of the external demand function on the
pumps
The effect on the internal circulation pump is selected
in coding address 3F in the
"General"
group.
The effect on the relevant heating circuit pump is
selected in coding address d7 in the
"Heating circuit"
group.
The effect on a circulation pump for cylinder heating is
selected in coding address 5F in the
"DHW"
group.
DHW circulation pump runtime for brief operation
The DHW circulation pump is started by closing the
contact at DE1, DE2 or DE3 by means of a pushbut-
ton. The runtime is adjusted via coding address "3d" in
the
"General"
group.
Analogue input 0
–
10 V
The 0
–
10 V hook-up provides an additional set boiler
water temperature:
0
–
1 V is taken as "no set boiler water temperature
default".
1 V
≙
Set value 10 °C
10 V
≙
Set value 100 °C
Ensure DC separation between the earth conductor
and the negative pole of the on-site power source.
Output
aBJ
The following functions can be connected to output
aBJ
:
■
Feed pump to substation
or
■
DHW circulation pump
or
■
Fault message facility
Information regarding the feed pump
Function only possible in conjunction with a heating
circuit control unit connected via LON.
Information on DHW circulation pumps
Connect DHW circulation pumps with standalone func-
tions directly to the 230 V
∼
supply.
Function assignment
Select the function of output
aBJ
via coding address
"36" in the
"General"
group at the boiler control unit.
Control functions
External operating program changeover
The "External operating program changeover" function
is implemented via the EA1 extension. There are 3
inputs available at the EA1 extension (DE1 to DE3).
The function is selected via the following coding
addresses in the
"General"
group:
Heating program changeover
Code
Input DE1
3A:1
Input DE2
3b:1
Input DE3
3C:1
Select the operating program changeover function for
the respective heating circuit at the boiler control unit,
via coding address "d8" in the
"Heating circuit"
group:
Function description
External extensions (accessories)
(cont.)
5775 636 GB
Functions
Summary of Contents for C3TB
Page 136: ...136 Troubleshooting Repairs gas condensing module cont 5775 636 GB Diagnosis ...
Page 143: ...143 Parts lists Heat cell assembly 5775 636 GB Components ...
Page 160: ...160 Parts not shown 0009 PCB IU100 B30 Parts lists Fuel cell assembly 5775 636 GB Components ...
Page 161: ...161 Parts lists Fuel cell assembly cont 5775 636 GB Components ...
Page 187: ...187 5775 636 GB ...