Serial Interface Manual
TLS4/TLS-450 Monitoring Systems
Part No. 577013-950, Revision L
343
Function Code:
671
Version 3
Function Type:
Set Tank Density High Limit
Command Format:
Inquire:
Display:
<SOH>S671TTdd.ddd
<SOH>I671TT
Computer:
<SOH>s671TTFFFFFFFF
<SOH>i671TT
Notes:
1.
TT - Tank Number (Decimal, 00=all)
2.
dd.ddd - Density High Limit (Decimal)
Value Range = [42.139, 56.185] [US]
Value Range = [675.00, 900.00] [Metric]
3.
FFFFFFFF - Density High Limit (ASCII Hex IEEE float)
Typical Response Message, Display Format:
<SOH>
I671TT
JAN 22, 2010 3:16 PM
TANK DENSITY HIGH LIMIT
TANK PRODUCT LABEL LBS/FT^3
1 REGULAR UNLEADED 56.185
<ETX>
Typical Response Message, Computer Format:
<SOH>i671TTYYMMDDHHmmTTFFFFFFFF&&CCCC<ETX>
Notes:
1.
YYMMDDHHmm - Current Date and Time
2.
TT - Tank Number (Decimal, 00=all)
3.
FFFFFFFF - Density High Limit (ASCII Hex IEEE float)
Value Range = [41.139, 56.185]
4.
&& - Data Termination Flag
5.
CCCC - Message Checksum