Serial Interface Manual
TLS4/TLS-450 Monitoring Systems
Part No. 577013-950, Revision L
601
Function Code:
B7E
Version 1
Function Type:
Pressure Line Leak Pressure Offset Monitor Report
Command Format:
Display:
<SOH>IB7EQQ
Computer:
<SOH>iB7EQQ
Typical Response Message, Display Format:
<SOH>
IB7EQQ
JAN 1, 2000 2:56 PM
PRESSURE LINE LEAK PRESSURE OFFSET MONITORS REPORT
Q 1:REGULAR UNLEADED
P0: PASS
LAST UPDATE: 21 DAYS
Pd: FAIL
LAST UPDATE: 44 DAYS
Pd= 40.1 PSI
Pd Ref=32.3 PSI
Pv: PASS
Pv =28.1 PSI
Pon=44.1 PSI
Pd =40.1 PSI
Pf: PASS
MIN = 22.5 PSI
MAX = 37.9 PSI
<ETX>
Typical Response Message, Computer Format:
<SOH>IB7EQQYYMMDDHHmmQQAABBBBCCDDDDEEEEEEEEFFFFFFFF
GGHHHHHHHHIIIIIIIIJJJJJJJJ...
QQAABBBBCCDDDDEEEEEEEEFFFFFFFF
GGHHHHHHHHIIIIIIIIJJJJJJJJ&&CCCC<ETX>
Notes:
1.
YYMMDDHHmm - Current Date and Time
2.
QQ - Pressure Line Leak sensor number (Decimal, 00=All)
3.
AA - P0 pass/fail status
00=fail
01=pass
4.
BBBB - P0 last update in days
5.
CC - Pd pass/fail status
00=fail
01=pass
6.
DDDD - Pd last update in days
7.
EEEEEEEE - Pd in PSI (ASCII Hex IEEE float)
8.
FFFFFFFF - Pd Ref in PSI (ASCII Hex IEEE float)
9.
GG - Pd pass/fail status
00=fail
01=pass
10.
HHHHHHHH - Pv in PSI (ASCII Hex IEEE float)
11.
IIIIIIII - Pon in PSI (ASCII Hex IEEE float)
12.
JJJJJJJJ - Pd in PSI (ASCII Hex IEEE float)
13.
&& - Data Termination Flag
14.
CCCC - Message Checksum