Function Code:
A9G
Version 1
Function Type:
Power Outage Inventory Report Date/Time Based
Command Format:
Display:
<SOH>IA9GTTyymmddYYMMDDnnn
Computer:
<SOH>iA9GTTyymmddYYMMDDnnn
Notes:
1.
yymmdd - Starting date (000000 = no starting date)
2.
YYMMDD - Ending Date (000000 = no ending date))
3.
nnn - Maximum Records [001…999] (10 = default) (decimal)
4. If no data is entered or zeros are entered for the starting
date, ending date and maximum records, the last 10 records
will be returned.
Typical Response Message, Display Format:
<SOH>
IA9GTT
JAN 22, 2007 3:24 PM
STATION HEADER 1....
STATION HEADER 2....
STATION HEADER 3....
STATION HEADER 4....
Volume=GALLONS
Height=INCHES
POWER OUTAGE REPORT Temp=FAHRENHEIT
Selected Range:
All Records:
Tank 1:UNLEADED FUEL WATER TEMP
INCREASE DATE / TIME VOLUME VOLUME
POWER REMOVED: AUG 15, 2013 15:53:38 9086 0 74.4
POWER RESTORED: AUG 15, 2013 15:54:55 9026 0 74.4
GROSS VOLUME CHANGE: -60
<ETX>
Typical Response Message, Computer Format:
<SOH>iA9GTTYYMMDDHHmmTTnnnnYYMMDDHHmmYYMMDDHHmmNNFFFFFFFF...
YYMMDDHHmmYYMMDDHHmmNNFFFFFFFF...
TTnnnnYYMMDDHHmmYYMMDDHHmmNNFFFFFFFF...
YYMMDDHHmmYYMMDDHHmmNNFFFFFFFF&&CCCC<ETX>
Notes:
1.
YYMMDDHHmm - Current Date and Time
2.
TT - Tank Number (Decimal, 00=all)
3.
nnnn - Number of History Records to follow (Decimal)
4.
YYMMDDHHmm - Power Removed Date/Time
5.
YYMMDDHHmm - Power Restore Date/Time
6.
NN - Number of eight character Data Fields to follow (Hex)
7.
FFFFFFFF - ASCII Hex IEEE floats:
1. Power Removed Fuel Volume
2. Power Remove Water Volume
3. Power Removed Temperature
4. Power Restored Fuel Volume
5. Power Restored Water Volume
6. Power Restored Temperature
7. Gross Change
8.
&& - Data Termination Flag
9.
CCCC - Message Checksum