Serial Interface Manual
TLS4/TLS-450 Monitoring Systems
Part No. 577013-950, Revision L
342
Function Code:
64B
Version 33
Function Type:
Set Tank Water Alarm Filter Delay
Command Format:
Inquire:
Display:
<SOH>S64BTTf
<SOH>I64BTT
Computer:
<SOH>s64BTTf
<SOH>i64BTT
Notes:
1.
TT - Tank Number (Decimal, 00=all)
2.
f - Water alarm delay level
3. The set command is only operational for the water alarm filter level OFF.
For filter levels Low, Medium and High the delay time is fixed at 180
seconds.
Typical Response Message, Display Format:
<SOH>
I64B00
JAN 22, 2010 3:12 PM
WATER ALARM FILTER DELAY
TANK PRODUCT LABEL
1
REGULAR 30 S
2
MID GRADE 120 S
3
PREMIUM 180 S
<ETX>
Typical Response Message, Computer Format:
<SOH>i64BTTYYMMDDHHmmTTf...
TTf&&CCCC<ETX>
Notes:
1.
YYMMDDHHmm - Current Date and Time
2.
TT - Tank Number (Decimal)
3.
f - Tank Water Alarm Filter Delay
1 = 30 seconds
2 = 60 seconds
3 = 90 seconds
4 = 120 seconds
5 = 150 seconds
6 = 180 seconds
4.
&& - Data Termination Flag
5.
CCCC - Message Checksum