Serial Interface Manual
TLS4/TLS-450 Monitoring Systems
Part No. 577013-950, Revision L
256
Function Code 5P1:
(Continued)
EVENT-ID - 0005
EVENT – Gross Test Fail Alarm: T 1: REGULAR, T 2: UNLEADED
EVENT – Sudden Loss Alarm: T 1: REGULAR, T 2: UNLEADED, T3: DIESEL
REPORT – Alarm History Report, Tank Leak History Report
CONTACT – FMS, Sheetz Maintenance
CON. MODE – FAX - Co 1 : Modem 1 Label
------
EVENT-ID - 0006
EVENT – Gross Test Fail Alarm: T 1: REGULAR, T 2: UNLEADED
EVENT – Sudden Loss Alarm: T 1: REGULAR, T 2: UNLEADED, T3: DIESEL
ACTION - Auto Connect
CONTACT – Sheetz Mgmt.
CON. MODE – Computer – Co 3 : TCP/IP 1 Label
------
<ETX>
Typical Response Message, Computer Format:
<SOH>i5P100YYMMDDHHmmIIIIT
(if T=0)
<SOH>i5P100YYMMDDHHmmIIIITttnnMMWWwwDDhhmmss
(if T=1)
<SOH>i5P100YYMMDDHHmmIIIITGGTTEAANNnnDD...
(if T=2 and E=0)
nnDD...
(if T=2 and E=1)
OOnnDD...
(if T=2 and E=2)
A<ETX> (if A=0)
ALLDD&&CCCC<ETX> (if A=1)
APPnnRRR...&&CCCC<ETX> (if A=2)
AWWnnRRR...nnCC...&&CCCC<ETX> (if A=3)
Notes:
1.
YYMMDDHHmm - Current Date and Time
2.
IIII - AutoEventID
For Inquire, 0000 means “all”.
For Add only 0000 is valid.
For Delete, only 0001-9999 is valid.
For DeleteAll, 0000 should be used.
3.
T - Trigger Type
0=Trigger Not Set
1=Trigger on Time
2=Trigger on Event
3=Trigger AutoXmit
4.
A - Action Type
0=Action Not Set
1=Action on Device
2=Action Print Report
3=Action Auto Connect
4=Action AutoXmit
5.
tt - Task Period (see command 5P3)
6.
nn - Number of 2-digit entries to follow
See explanation for “nn” in function i5P300
7.
MM - Month (see command 5P3)
8.
WW -
Occurrence of day-of-week in month (see command 5P3)
9.
ww - Day of Week
(see command 5P3)
10.
DD - Day of Month
(see command 5P3)
11.
hh -
Hour of day
(see command 5P3)
12.
mm - Minute of hour
(see command 5P3)
13.
GG - Number of Triggers to follow
(see command 5P4)
14.
TT - Trigger Number
(see command 5P4)
15.
E - Trigger Event Group
(see command 5P4)
16.
AA - Alarm/Warning Category:
(see command 5P4)