Serial Interface Manual
TLS4/TLS-450 Monitoring Systems
Part No. 577013-950, Revision L
286
Function Code:
60K
Version 1
Function Type:
Set Probe Number Installed in Tank
Command Format:
Inquire:
Display:
<SOH>S60KTTpp
<SOH>I60KTT
Computer:
<SOH>s60KTTpp
<SOH>i60KTT
Notes:
1.
pp - -1 if tank not assigned to probe
2.
00=all, inquiry only
Typical Response Message, Display Format:
<SOH>
I60KTT
MAR 26, 2007 1:50 PM
TANK INSTALLED PROBE NUMBER CONFIGURATION
TANK LABEL PROBE NUM
1 REGULAR UNLEADED 1
<ETX>
Typical Response Message, Computer Format:
<SOH>i60KTTYYMMDDHHmmTTpp...
TTpp&&CCCC<ETX>
Notes:
1.
YYMMDDHHmm - Current Date and Time
2.
TT - Tank Number (Decimal, 00=all)
3. pp -Probe Number to configure to tank (pp = -1 if not assigned)
4.
&& - Data Termination Flag
5.
CCCC - Message Checksum