Serial Interface Manual
TLS4/TLS-450 Monitoring Systems
Part No. 577013-950, Revision L
336
Function Code:
63H
Version 2
Function Type:
Set Accuchart Delete Chart
Command Format:
Inquire:
Display:
<SOH>S63HTT149II
<SOH>I63HTT
Computer:
<SOH>s63HTT149II
<SOH>i63HTT
Notes:
1.
TT - Tank Number [01..32], (Decimal, set for primary tank)
2.
II - Chart ID number [02…99]
3.
Chart ID=1 always exists. It cannot be deleted.
4.
Set operation requires AccuChart to be installed.
Typical Response Message, Display Format:
<SOH>
I63HTT
JAN 24, 2009 2:52 PM
TANK CHARTS
TANK CHART ID STATUS
---- -------- ------------
01 01 ACTIVE CHART
02 READY CHART
06
BAD POINT CHART
07
INCOMPLETE CHART
08
CALCULATING CHART
02 01 ACTIVE CHART
06
READY CHART
07
BAD POINT CHART
08
INCOMPLETE CHART
09
CALCULATING CHART
<ETX>
Typical Response Message, Computer Format:
<SOH>i63HTTYYMMDDHHmmTTNNIIs...IIs
TTNNIIs...IIs&&CCCC<ETX>
Notes:
1.
YYMMDDHHmm - Current Date and Time
2.
TT - Tank Number [01..32], (Decimal, 00=all)
3.
NN - Number of charts [00…99] (Decimal)
4.
II - Chart ID Number [01…99] (Decimal)
5.
s - Status
0=Active Chart
1=Ready Chart
2=Incomplete Chart
3=Bad Point Chart
4=Calculating Chart
6.
&& - Data Termination Flag
7.
CCCC - Message Checksum