Serial Interface Manual
TLS4/TLS-450 Monitoring Systems
Part No. 577013-950, Revision L
48
Function Code 202 Notes:
(Continued)
Typical Response Message, Computer Format:
<SOH>i202TTYYMMDDHHmmTTpddYYMMDDHHmmYYMMDDHHmmNNFFFFFFFF...
TTpddYYMMDDHHmmYYMMDDHHmmNNFFFFFFFF&&CCCC<ETX>
Notes:
1.
YYMMDDHHmm - Current Date and Time
2.
TT - Tank Number (Decimal, 00=all)
3.
p - Product Code (one ASCII character [20h-7Eh])
4.
dd - Number of Deliveries to follow (Decimal, 00 if no data
available for this tank)
5.
YYMMDDHHmm - Starting Date/Time
6.
YYMMDDHHmm - Ending Date/Time
7.
NN - Number of eight character Data Fields to follow (Hex)
8.
FFFFFFFF - ASCII Hex IEEE floats:
1. Starting Volume
2. Starting TC Volume
3. Starting Water
4. Starting Temp
5. Ending Volume
6. Ending TC Volume
7. Ending Water
8. Ending Temp
9. Starting Height
10. Ending Height
9.
&& - Data Termination Flag
10.
CCCC - Message Checksum