Serial Interface Manual
TLS4/TLS-450 Monitoring Systems
Part No. 577013-950, Revision L
408
Function Code:
784
Version 1
Function Type:
Set Pressure Line Leak Shutdown Rate
Command Format:
Inquire:
Display:
<SOH>S784QQrr
<SOH>I784QQ
Computer:
<SOH>s784QQrr
<SOH>i784QQ
Typical Response Message, Display Format:
<SOH>
I784QQ
JAN 24, 2000 2:54 PM
PRESSURE LINE LEAK SHUTDOWN RATE
LINE SHUTDOWN RATE
Q 1:REGULAR UNLEADED 3.0 GPH
<ETX>
Typical Response Message, Computer Format:
<SOH>i784QQYYMMDDHHmmQQrr...
QQrr&&CCCC<ETX>
Notes:
1.
YYMMDDHHmm - Current Date and Time
2.
QQ - Pressure Line Leak sensor number (Decimal, 00=All)
3.
rr - Shutdown rate
01=0.10 gal/hr
02=3.00 gal/hr
03=0.20 gal/hr
04=None
4.
&& - Data Termination Flag
5.
CCCC - Message Checksum