Serial Interface Manual
TLS4/TLS-450 Monitoring Systems
Part No. 577013-950, Revision L
407
Function Code:
783
Version 1
Function Type:
Set Pressure Line Leak 0.10 GPH Test Schedule
Command Format:
Inquire:
Display:
<SOH>S783QQf
<SOH>I783QQ
Computer:
<SOH>s783QQf
<SOH>i783QQ
Typical Response Message, Display Format:
<SOH>
I783QQ
JAN 24, 1996 2:54 PM
PRESSURE LINE LEAK 0.10 TEST SCHEDULE
LINE 0.10 GPH TEST
Q 1:REGULAR UNLEADED DISABLED
<ETX>
Typical Response Message, Computer Format:
<SOH>i783QQYYMMDDHHmmQQf...
QQf&&CCCC<ETX>
Notes:
1.
YYMMDDHHmm - Current Date and Time
2.
QQ - Pressure Line Leak sensor number (Decimal, 00=All)
3. f - 0.10 GPH Test Schedule
0=Disabled
1=Repetitive
2=Auto
3=Manual
4.
&& - Data Termination Flag
5.
CCCC - Message Checksum