Serial Interface Manual
TLS4/TLS-450 Monitoring Systems
Part No. 577013-950, Revision L
337
Function Code:
641
Version 3
Function Type:
Set Density Code
Command Format:
Inquire:
Display:
<SOH>S641PPSSSSSSSSSSSSSS
<SOH>I641PP
Computer:
<SOH>s641PPSSSSSSSSSSSSSS
<SOH>i641PP
Notes:
1. SSSSSSSSSSSSSS - Density Code (Entry is 14 characters or empty))
Typical Response Message, Display Format:
<SOH>
I641PP
JAN 22, 2010 3:16 PM
DENSITY FLOAT CODE
PROBE CODE
1
B7053686719512
2
3
A7058696729713
4
B7056772719214
<ETX>
Typical Response Message, Computer Format:
<SOH>i641PPYYMMDDHHmmPPNNSSSSSSSSSSSSSS…&&CCCC<ETX>
Notes:
1.
YYMMDDHHmm - Current Date and Time
2.
PP - Probe Number (Decimal, 00=all)
3.
NN - Number of characters to follow
4. SSSSSSSSSSSSSS - Density Code
5.
&& - Data Termination Flag
6.