Serial Interface Manual
TLS4/TLS-450 Monitoring Systems
Part No. 577013-950, Revision L
356
Function Code:
6C9
Version 1
Function Type:
Set Tank Delivery Required Limit for Tall Tanks
Command Format:
Inquire:
Display:
<SOH>S6C9TTGGGGGGGGGGGG
<SOH>I6C9TT
Computer:
<SOH>s6C9TTFFFFFFFF
<SOH>i6C9TT
Notes:
1.
TT - Tank Number (Decimal, 00=all)
2.
GGGGGGGGGGGG - Delivery Required Limit, Gallons (Decimal)
3.
FFFFFFFF - Delivery Required Limit, Gallons (ASCII Hex IEEE float)
Typical Response Message, Display Format:
<SOH>
I6C9TT
JAN 22, 1996 3:19 PM
TANK DELIVERY REQUIRED LIMIT
TANK LABEL
GALLONS PERCENT
1 TANK 1 2000000 20
<ETX>
Typical Response Message, Computer Format:
<SOH>i6C9TTYYMMDDHHmmTTFFFFFFFF...
TTFFFFFFFF&&CCCC<ETX>
Notes:
1.
YYMMDDHHmm - Current Date and Time
2.
TT - Tank Number (Decimal, 00=all)
3.
FFFFFFFF - Delivery Required Limit, Gallons (ASCII Hex IEEE float)
4.
&& - Data Termination Flag
5.
CCCC - Message Checksum