Serial Interface Manual
TLS4/TLS-450 Monitoring Systems
Part No. 577013-950, Revision L
441
Function Code:
79C
Version 2
Function Type:
Set Daily Manual Adjustment Value
Command Format:
Inquire:
Display:
<SOH>S79CTTMMDDGGGGGG
<SOH>I79CTTMMDD
Computer:
<SOH>s79CTTMMDDFFFFFFFF
<SOH>i79CTTMMDD
Notes:
1.
TT - Tank Number
2.
MMDD - Month and Day
3.
GGGGGG - Adjustment Value, Gallons (Decimal)
4.
FFFFFFFF - Adjustment Value, Gallons (ASCII Hex IEEE float)
Typical Response Message, Display Format:
<SOH>
I79CTT
JAN 22, 2009 3:24 PM
T 1:REGULAR UNLEADED
MAR 26 ADJ VOL: 300
<ETX>
Typical Response Message, Computer Format:
<SOH>i79CTTYYMMDDHHmmTTMMDDFFFFFFFF&&CCCC<ETX>
Notes:
1.
YYMMDDHHmm - Current Date and Time
2.
TT - Tank Number
3.
MMDD - Month and Day
4.
FFFFFFFF - Adjustment Value, Gallons (ASCII Hex IEEE float)
5.
&& - Data Termination Flag
6.