Serial Interface Manual
TLS4/TLS-450 Monitoring Systems
Part No. 577013-950, Revision L
616
Function Code C02:
(Continued)
Typical Response Message, Computer Format:
<SOH>iC02PPYYMMDDHHmmGGPPnnTT...YYMMDDHHmmYYMMDDHHmmNNFFFFFFFF...
PPnnTT...YYMMDDHHmmYYMMDDHHmmNNFFFFFFFF&&CCCC<ETX>
Notes:
1.
YYMMDDHHmm - Current Date and Time
2.
GG - Number of product Groupings to follow (Hex)
3.
PP - Product Number (Decimal, 00=All Products)
4.
nn - Number of tanks that are mapped to the product (Decimal)
5.
TT - Tank numbers mapped to product
6.
YYMMDDHHmm - Opening Date and Time
7.
YYMMDDHHmm - Closing Date and Time
8.
NN - Number of eight character Data Fields to follow (Hex)
9.
FFFFFFFF - ASCII Hex IEEE floats:
1. Probe measured inventory at previous period close
2. Sum total of adjusted deliveries during period
3. Sum total of all metered sales during period
4. Manually entered adjustments for period
5. Calculated Inventory Volume at period close
6. Probe measured inventory at period close
7. Water Height at period close
8. Variance over period
10.
&& - Data Termination Flag
11.