Serial Interface Manual
TLS4/TLS-450 Monitoring Systems
Part No. 577013-950, Revision L
123
Function Code:
306
Version 1
Function Type:
Vapor Sensor Status Report
Command Format:
Display:
<SOH>I306SS
Computer:
<SOH>i306SS
Typical Response Message, Display Format:
<SOH>
I306SS
JAN 28, 1995 10:11 AM
STATION HEADER 1....
STATION HEADER 2....
STATION HEADER 3....
STATION HEADER 4....
VAPOR STATUS REPORT
SENSOR LOCATION STATUS
1 VAPOR # 1 NORMAL
<ETX>
Typical Response Message, Computer Format:
<SOH>i306SSYYMMDDHHmmSSssss...
SSssss&&CCCC<ETX>
Notes:
1.
YYMMDDHHmm - Current Date and Time
2.
SS - Sensor Number (Decimal, 00=all)
3.
ssss - Sensor Status Value:
0000=Sensor Normal
0001=Sensor Setup Data Warning
0002=Sensor Fuel Alarm
0003=Sensor Out Alarm
0004=Sensor Short Alarm
0005=Sensor Water Alarm
0006=Sensor Water Out Alarm
0007=Sensor High Liquid Alarm
0008=Sensor Low Liquid Alarm
0009=Sensor Liquid Warning
4.
&& - Data Termination Flag
5.
CCCC - Message Checksum