X5 AC Drive User’s Manual
Chapter 6: Using Macro Mode / Quick Start
DPD00089A
-
69 -
© 2009 Vacon Incorporated All Rights Reserved
6.4
Getting a Quick Start
The following basic procedure is for operators using simple applications who would like to get
started quickly.
Be sure to read and understand all the sections in this chapter before proceeding
with these instructions.
If you are using remote operators, substitute the speed potentiometer for the
INC and DEC (up and down arrow) keys, and the remote Run/Stop switch for the FWD key in the
following instructions.
1. Follow all precautions and procedures in “Chapter 3: Receiving and Installation” on page 24.
2. Find the motor nameplate, and using parameters
509 (Rated Mtr Volt)
510 (Rated Mtr FLA)
,
511 (Rated Mtr RPM)
, and
, set up the motor parameters appropriately.
Parameter
should also be set up accurately so the drive can run its routine to
measure motor stator resistance. (See “Measuring Stator Resistance (RS Measurement)” on
page 51.)
3. Apply AC power to the input terminals. For about 2 seconds the display will show all segments
active. The display then changes to zeros.
4. The factory settings are for keypad-only operation in the forward direction—that is, the REV key
is disabled. Press the
FWD
key, which causes the FWD indicator to illuminate.
5. Press the
INC
key to increase the desired running frequency. When the display gets to
0.1 Hz
,
the drive starts to produce an output.
6. When the motor starts to turn, check the rotation. If the motor is turning in the wrong direction,
press STOP, remove AC power, and wait for all indicators to go out
.
After the STATUS
indicator has gone out, reverse any two of the motor leads at T1/U, T2/V, or T3/W.
7. The X5 drive is preset to run a typical NEMA B 4-pole induction motor to a maximum speed of
60.0 Hz
with both acceleration and deceleration times set to
5.0 seconds
.
8. Use the
INC
and
DEC
keys to set the proper running speed of the motor and the
FWD
and
STOP
keys to control its operation.
Note
that the X5 external cooling fans operate continuously for the first five minutes of power-up
time; after this point, they operate only as needed to control the operating temperature of the drive.
IMPROPER EQUIPMENT COORDINATION
Verify that proper voltage is connected to the drive before applying power.
Failure to observe this instruction can result in injury or equipment damage.
CAUTION
MAUVAISE COORDINATION DES APPAREILS
Vérifiez que l’onduleur est raccordée à la bonne tension avant de le mettre sous tension.
Si cette directive n’est pas respectée, cela peut entraîner des blessures corporelles ou des
dommages matériels.
ATTENTION