205 Vin1 Config
Default = 0-10V
Range: n/a
Level: 2
Parameter
205, Vin1 Config,
selects the type of signal for analog input Vin1. Vin1 can be voltage, current, or pulse train
input. This parameter also determines input range, impedance, and characteristics. Use
206 (Vin1 Offset)
and
to customize the selected range. The following data values may be assigned to this parameter:
Parameter Value
Description
0-10V
0-10Vdc signal. This is the selection that is recommended when the drive is following the 6FS or 48FS
output of another drive.
0-10V Brk W
0-10Vdc signal with broken wire detection for speed pot operation
0-10V I
0-10Vdc signal Inverted
0-10V Bipol
0-10Vdc signal
(5Vdc is stop with 0Vdc Full Rev and 10Vdc Full FWD)
0-5V
0-5Vdc signal
0-5V I
0-5Vdc signal Inverted
0-20mA 250
0 to 20 mA current signal with 250 Ohm load
0-20mA 250I
0 to 20 mA current signal with 250 Ohm load Inverted
4-20mA 250
4 to 20 mA current signal with 250 Ohn load load
4-20mA 250I
4 to 20 mA current signal with 250 Ohm load Inverted
PT 0-1kHz
0 to 1 kHz pulse train
PT 0-10kHz
0 to 10 kHz pulse train
PT 0-100kHz
0 to 100 kHz pulse train
Inverted signal response means that minimum input signal produces maximum inverter output frequency and maximum
input signal produces minimum output frequency.
206 Vin1 Offset
Default = 0.00%
Range: 0.0 to 100.0%
Level: 2
Parameter
206, Vin1 Offset,
configures the input range (offset) for analog input Vin1 that will affect speed or torque
limit functions. It is expressed as a percentage of the maximum value of the input signal.
Note that if the input signal drops below the offset value or if the input signal is lost (if no offset is configured), fault 22
will be generated.
207 Vin1 Span
Default = 100%
Range: 10.0 to 200.0%
Level: 2
Parameter
207,
the
Vin1 Span
parameter, is used to alter the input range (span) of the input signal for analog input
Vin1 that will affect speed or torque limit functions. For example, if
parameter
205, Vin1 Config
,
selects the 0 to 10 Vdc
input signal, setting this parameter to 50% reduces it to 0 to 5 Vdc.
208 Cin Config
Default = 0-20mA 50
Range: n/a
Level 2
Parameter
208, Cin Config,
selects the type of signal for analog input Cin. Parameters
(Cin Offset)
(Cin
Span)
may be used to customize the selected range. The following data values may be assigned to this parameter:
Parameter Value
Description
4-20mA 50
4 to 20 mA current signal with 50 Ohm load
4-20mA 50I
4 to 20 mA current signal with 50 Ohm load Inverted
0-20mA 50
0 to 20 mA current signal with 50 Ohm load
0-20mA 50I
0 to 20 mA current signal with 50 Ohm load Inverted
Inverted signal response means that minimum input signal produces maximum inverter output frequency and maximum
input signal produces minimum output frequency.
209 Cin Offset
Default = 0.0%
Range: 0.0% to 100.0%
Level: 2
Parameter
209, Cin Offset,
configures the offset for analog input Cin expressed as a percentage of the maximum value
Table 7-2: Description of X5 Parameters