X5 AC Drive User’s Manual
Chapter 7: X5 Parameters
DPD00089A
-
99 -
© 2009 Vacon Incorporated All Rights Reserved
801 Program Number
Default: 0
Range: 0 to 9999
Level 2, Macro
This parameter (Special Program Number) provides a way of enabling hidden functions in the drive and storing
parameters to the customer set.
Data Value
Special Function Configured
0
Standard program
1
Reset all parameters to factory default values (display = SETP).
2
Store customer parameter values (display = STOC).
3
Load customer parameter values (display = SETC).
4
Swap active parameters with customer stored settings.
Reset Total Run Time, parameter
108
.
20
Enable writing of today’s time and today’s date parameter.
21
Store today’s time and today’s date parameter to RTC chip.
22
Abort time writing process.
30
Re-calibrate analog inputs (NOTE: no signal should be attached when performing this).
40
Clear Keeper records.
50
Allow model-dependent parameters to be recalled by USB. (See
“Recalling Drive Parameters” on
.
Note
that data value 50
must
be used to recall the following parameters via USB:
503
V/Hz Knee Freq
514
Motor RS
509
Rated Mtr Volt
515
Power Factor
510
Rated Mtr FLA
517
Single Phase
511
Rated Mtr RPM
Note also
that the following parameters will
never
be recalled via USB:
490
Appl Macro
900
SIO Protocol
794
Drive Name
901
SIO Baud Rate
799
USB Config Mode
902
Comm Drop #
810
Language
916
Infrared Baud
811
Access Code
80
Disable Daylight Savings Time.
81
Enable Daylight Savings Time.
802 Start Options
Default: LS Lockout
Range: n/a
Level 2
The Start Options parameter configures the Line Start Lockout functionality of the drive. All data values ending with “2”
allow you to press the
Enter
key to store the customer speed reference value on the keypad. You must press and hold
the
Enter
key for two seconds to save the speed command. The following data values may be assigned:
Data Value
Description
LS Lockout
(Line Start Lockout). If maintained contact run operators are used, they must be opened and then
re-closed for the drive to start after AC power is applied.
AutoStart
When AC power is applied, if a Run command is present through the terminal strip, the drive will
start.
LSL w/FLY
This setting has both LS Lockout and Catch on the Fly enabled at the same time.
Auto w/FLY
This setting has both Auto-Start and Catch on the Fly enabled at the same time.
LS Lockout2
(Line Start Lockout). If maintained contact run operators are used, they must be opened and then
re-closed for the drive to start after AC power is applied.
AutoStart2
When AC power is applied, if a Run command is present through the terminal strip, the drive will
start.
LSL w/FLY 2
This setting has both LS Lockout and Catch on the Fly enabled at the same time.
Auto w/FLY2
This setting has both Auto-Start and Catch on the Fly enabled at the same time.
Table 7-2: Description of X5 Parameters
(Page 29 of 40)