X5 AC Drive User’s Manual
Chapter 7: X5 Parameters
DPD00089A
-
107 -
© 2009 Vacon Incorporated All Rights Reserved
917 Fbus Port Config
Default: 485 w/ctl
Range: n/a
Level 2 (SIO)
This parameter is used for configuring the Fieldbus port.
The following data values may be assigned to this parameter:
Parameter Value
0 = Disabled; no Fieldbus communications allowed.
1 = 485 w/ctl: The RS485 port will be re-mapped to Fieldbus Communications.
2 = IR w/ctl: The Infrared port will be re-mapped to Fieldbus Communications; serial link control can only come through
Fieldbus communications.
3 = IR no ctl: The Infrared port will be re-mapped to Fieldbus Communications, but no control will be allowed through
Fieldbus. The RS-485 port on the drive will still have SIO control rights.
920 SIO Vmet Level
Default: 100.00%
Range: 0.00-100.00%
Level 2 (SIO)
This parameter allows the Vmet Analog Output level to be programmed to a certain voltage, if
Vmet Config
is set for
SIO Config
.
921 SIO Imet Level
Default: 100.00%
Range: 0.00-100.00%
Level 2 (SIO)
This parameter allows the Imet Analog Output level to be programmed to a certain voltage, if
Imet Config
is set for
SIO
Config
.
926 Status Word 2
Default: Read-only
Range: n/a
Level 2 (SIO)
This parameter provides status information for the drive operation to a serial link user.
The following data values may be assigned to this parameter:
Bit # / Value
0 = Reminder 1 Time Expired
1 = Reminder 2 Time Expired
2 = Reminder 3 Time Expired
Table 7-2: Description of X5 Parameters