X5 AC Drive User’s Manual
Chapter 8: Troubleshooting
DPD00089A
-
130 -
© 2009 Vacon Incorporated All Rights Reserved
38
OP BRD Flt
Fault on options
board
0
Loss of communication between
option board and drive.
Check connections. Consult
factory.
1
Could not identify option board
Consult factory.
2
The option board does not match
the last option board ID that was
active when the drive was
powered down.
Check and reconfigure option
board setup.
3
Option board ID is unsupported.
Consult factory.
4
Comm option board does not
have the proper daughter card
installed.
Consult factory.
5
Internal problem.
Consult factory.
6
Network communications error.
Check connections and setup.
7
Option board has been removed. Reconfigure.
39
Fan Loss
Loss of fan control or
operation
0
There is a problem with the heat
sink fan.
Consult factory.
1
There is a problem with the
internal fan. This occurs only on
Size 4 and 5 models. All other
models display a fan error
warning.
Note that this is lack of fan
control, so the fan can be
spinning and this fault will still
occur. This can happen if the fan
is on and should not be, or if the
fan feedback signals are
obstructed from getting to the
control board.
Table 8-1: X5 Fault Codes
(Page 6 of 6)
Code
Fault Display
Description
Adv. Fault
Code
Explanation
Suggestions for Recovery
Note:
Shaded faults are auto-resettable, except where noted.