858 PID Low Corr
Default: 0.00%
Range: 0.00-100.00%
Level 2
This parameter sets the low limit of the PID output.
859 PID Deriv Gain
Default: 0.00%
Range: 0-2000
Level 2
The PID Derivative Gain parameter configures the derivative gain that is applied to the PID control.
Note:
Value must be greater than 0 for this to be active.
860 PID Sleep Cfg
Default: 0
Range: n/a
Level 2
861 (PID Sleep Lvl )
for the sleep threshold.
The following data values may be assigned to this parameter:
Parameter Value
Description
0
Disabled
1
PID Fbk <
2
PID Fbk >
3
PID Ref <
4
PID Ref >
5
PID Out >
6
PID Out <
861 PID Sleep Lvl
Default: 0.00%
Range: 0.00-100.00%
Level 2
This parameter sets the sleep level for the PID output.
862 PID Wake-up Lvl
Default: 100.00%
Range: 0.00-100.00%
Level 2
parameter
861
), with this parameter set to 10% the drive will awaken at 50% of the
process range.
863 Sleep Delay Time
864 Wake-up Delay
Default: 0.0 sec
Range: 0.0 - 300.0 sec
Level 2
These parameters set the sleep and wake-up delay times for the PID output.
865 PID Feedback
Default: Read-only
Range: n/a
Level 2
This is a view of the processed feedback signal after scaling (via span and offset).
866 PID Reference
Default: Read-only
Range: n/a
Level 2
This parameter sets the reference point for the PID output.
867 PID User Units
Default: 0
Range: n/a
Level 2
This parameter is for rescaling parameters
and
in user units relative to the process rather than in
percentage of full scale.
The following data values may be assigned to this parameter:
Parameter Value
Description
0
No
1
Yes
Table 7-2: Description of X5 Parameters