Sequencer Output Configuration
The X5 Program Sequencer allows digital outputs to be activated during states of the sequencer. This
function could be used to activate other devices in a system or to signal to an operator when a part
of the sequence is active. The user sets the digital output by setting bits 13-15 of the control
parameter with a binary value, and then sets a digital output parameter with the option for that same
binary value. For example, if a control state was output configured for a binary value of 111, then
any digital output configured to “SeqOut-111” would be activated during that time. The following
chart shows the output configuration options for the X5 drive:
X5 Sequencer Control Selection
The X5 Program Sequencer allows several control selection options not available in the X4 Program
Sequencer. These new options allow a terminal strip control state, or a state that faults the drive.
Bits 10-12 of the state’s control parameter determine the control selection configuration for that state
of the sequence. See the following chart for control selection options:
Table 7-7: Output Selection Options
Binary Value
(refers to bits 13-15)
Definition (Output Configuration)
000
Any digital output (or relay output) configured for SeqOut-000 is active in this state.
001
Any digital output (or relay output) configured for SeqOut-001 is active in this state.
010
Any digital output (or relay output) configured for SeqOut-010 is active in this state.
011
Any digital output (or relay output) configured for SeqOut-011 is active in this state.
100
Any digital output (or relay output) configured for SeqOut-100 is active in this state.
101
Any digital output (or relay output) configured for SeqOut-101 is active in this state.
110
Any digital output (or relay output) configured for SeqOut-110 is active in this state.
111
Any digital output (or relay output) configured for SeqOut-111 is active in this state.
Table 7-8: Control Selection Options
Binary Value
(refers to bits 10-12)
Definition
000
The drive will be stopped while in a state configured with this control selection.
001
The drive will be running FWD while in a state configured with this control selection.
010
The drive will be running REV when configured with this control selection.
011
The drive will be injecting DC current when configured with this control selection.
100
The drive will be faulted with User Fault #1 when configured with this control selection.
101
The drive will be faulted with User Fault #2 when configured with this control selection.
110
The drive will be in control of a terminal strip digital input configuration or an SIO control
word configuration. In this state, any digital input configured to “Seq Fwd” will control the
drive through the terminals with two-wire control. If bit 0 is enabled in SIO Control Word,
then bits 2 and 3 determine if the drive is running forward, reverse, or is stopped.
111
Future use (drive will be stopped)