705 Relay 1 Select
706 Relay 2 Select
707 DO1 Select
708 DO2 Select
Default: Drv Fault
Default: Drv Run
Default: Drv Ready
Default: At Speed
Range for Parameters 705-708: n/a
Levels 1, 2 for Parameters 705-706
Level 2 for Parameters 707-708
These parameters configure what condition causes relays R1, R2, DO1, and DO2 to activate. Parameter
705
is
associated with relay R1;
706
with relay R2;
707
with DO1; and
708
with relay DO2. The following values are valid:
Parameter Value
Description
Drv Ready
The drive is ready. (The relay will be open in Fault and Low Voltage conditions.)
Drv Fault
A fault has occurred. (If automatic fault reset and re-start is enabled, only faults that cannot be
608 (Restart Number)
.)
Drive Run
The drive has received a direction command.
Running FWD
The motor is running Forward and the output frequency is above 0.5 Hz.
Running REV
The motor is running in Reverse and the output frequency is above 0.5 Hz.
Zero Speed
The drive is in Run mode, but the speed reference is 0 Hz.
At Speed
The drive has reached reference speed.
Freq Limit
The drive limit is active when the speed commanded exceeds the value of parameter
306, Preset
Freq 4
.
Freq Hyst
This is active when the speed exceeds parameter
307 (Preset Freq 5)
.
Current Lim
Current Limit mode is active.
High Temp
The temperature limit of the drive has been exceeded.
Local Mode
The keypad is the control path for reference speed and control functions.
SeqOut-000
Programmed sequence step active. SeqOut-
XXX
values are all status
SeqOut-001
outputs linked to a step in the program sequencer.
SeqOut-010
SeqOut-011
“Using the X5 Program Sequencer” on page 111
SeqOut-100
SeqOut-101
SeqOut-110
SeqOut-111
Thres 1
Active status of Threshold 1 for this output (see parameter
740
on page 96)
Active status of Threshold 2 for this output (see parameter
743
on page 97)
Active status of Timer 1 for this output (see parameter
746
on page 97)
Active status of Timer 2 for this output (see parameter
749
on page 97)
ARCTIC
When a digital output is configured to use this option, the output will be active when the Arctic Mode
is turning on the DB resistor. This option will turn on when the temperature drops below the Arctic
mode entry point, which is -7 degrees C. This will work even if Arctic Mode is not enabled.
DI-FWD
DI-REV
DI-xxx
values all refer to inputs on option cards;
DI-R/J
when the respective input is active, the respective
DI-EN
output listed here is set.
DI-MOL
DI1
DI2
DI-x
values all refer to inputs on the drive control board;
DI3
when the respective input is active, the respective
DI4
output listed here is set.
DI5
Reminder 1
User-defined reminder
Reminder 2
User-defined reminder
Reminder 3
User-defined reminder
SIO Config
Indicates the setting the output will respond to the value set in parameter
(Control Word 2)
TOD Inhibit
Indicates the drive is disabled based on the time set in TOD run enable parameters.
Table 7-2: Description of X5 Parameters