X5 AC Drive User’s Manual
Chapter 7: X5 Parameters
DPD00089A
-
92 -
© 2009 Vacon Incorporated All Rights Reserved
702 Imet Config
Default: Drive Load
Range: n/a
Level 2
This parameter configures the analog signal that will be applied to the Imet output pin. The following data values may
be assigned to this parameter:
Para. Value
Description
Range Limit
Freq Out
Output frequency of the drive
Parameter max freq.
Voltage Out
Voltage being supplied to the motor
Rated motor voltage
Current Out
Current being supplied to the motor
200% of drive rating
Drive Load
Calculated percentage of drive rating
200% of drive rating
Drive Temp
Calculation of total drive temp rating
100% of unit temp rating
Stator Freq
Commanded frequency
100% of input config
Power Out
Calculated power output of drive
250% of drive rating
+/- Load
Percentage torque of drive
-200 to +200% of drive rating
105
)
PID Fback
Allows the analog output to produce
a signal in proportion to the PID
feedback received.
Vin 1
Mirrors the status of the Vin1 input
910
)
0-100%
Cin
Mirrors the status of the Cin input
911
)
0-100%
Vin 2
Mirrors the status of the Vin2 input
912
)
0-100%
SIO Config
Allows the serial port to set the Imet
analog output through parameter
(SIO Imet Lvl)
(Control Word 2)
Encoder
Monitors the status of an encoder
connected to the drive through an option
board.
703 Imet Span
Default: 100%
Range: 0.0%-200.0%
Level 2
This parameter sets the span of the Imet analog output.
704 Imet Offset
Default: 0.0%
Range: 0.0%-90.0%
Level 2
This parameter sets the offset of the Imet analog output.
Table 7-2: Description of X5 Parameters
(Page 22 of 40)