
P/N CWSI-IM-C3K6 Rev. F
© 2017 Johnson Controls. All rights reserved. All specifications and other information shown were current as of document revision
date and are subject to change without notice.
9
Section 2 – Specifications and Compatibility
2.1 Specifications
Power Source: 120/240Vac 1A 50/60Hz .
Batteries: Two 12Vdc 4Ah sealed lead acid batteries connected in series for up to 24 hours standby
operation or two 12Vdc 7Ah sealed lead acid batteries connected in series for 60 hours standby
operation. Use only Genesis/Enersys batteries P/N NP4-12 for 24 hour standby or NP7-12 for 60 hour
standby.
Operating Temperature: 32 to 120 degrees F
Operating Humidity: 85% non condensing
Special Application NAC Circuits: Programmable Non-power Limited. 1 Class “A” (Style Z) or 2 Class
“B” (Style Y) Field selectable.
Class A ratings: 24 Volts DC @ 1 Amp
Class B ratings: 24 Volts DC @ 1 Amp each
Regulated NAC Circuits: Programmable Non-power Limited. 1 Class “A” (Style Z) or 2 Class “B” (Style
Y) Field selectable.
Class A ratings: 24 Volts DC @ 100 Milliamps
Class B ratings: 24 Volts DC @ 100 Milliamps
Dry Contact Alarm Relays:
4 N.O. common type rated 24 Vdc @ 1 Amp. resistive.
2 Form “C” programmable rated 24 Vdc @ 1 Amp. resistive.
Dry Contact Trouble Relays:
1 Form C common type rated 24 Vdc @ 1 Amp. resistive.
Trouble Input
N.C Input for connection to Keltron SDACT(-2)
Auxiliary output: Current 350 ma. Max coil resistance 14.6 ohms.
Transceiver Operating Frequency: 900 MHz band.
Signal to Noise Ratio: Minimum Signal -100.2dBM Maximum Noise -115.3dBM
Antenna Types: Omni, Yagi
RF Path Class: B
Transmission Format: Frequency Hopping Spread Spectrum.
Dimensions: 17” high, 17” wide, 3 ¼” deep
Enclosure: Powder coated 16 gauge steel
Weight: 29 Lbs.