P/N CWSI-IM-C3K6 Rev. F
© 2017 Johnson Controls. All rights reserved. All specifications and other information shown were current as of document revision
date and are subject to change without notice.
73
When an alarm is received by the CP-3600(+) one of the alarm relays A, B or C will trip and activate
the appropriate zone on the SDACT(-2) communicator. The SDACT(-2) will transmit its programmed
SIA code for that zone input to the central station along with the Point I.D. and SIA code from the CP-
3600(+). Acknowledging the alarm on the CP-3600(+) will only silence its internal sounder. The
sounder on the SDACT(-2) CANNOT be silenced by pressing the ALARM ACK key on the CP-3600(+).
The SDACT(-2) will silence its sounder and fully reset only when the CP-3600(+) RESET key is pressed
and the SDACT(-2) has finished communicating to the central station. A restore signal will be sent to
the central station upon resetting the CP-3600(+).
When a supervisory alarm is received by the CP-3600(+), the Alarm C relay will short causing a
supervisory transmission to be sent from Zone 3 on the SDACT(-2). Acknowledging the supervisory on
the CP-3600(+) will only silence its internal sounder. The sounder on the SDACT(-2) CANNOT be
silenced by pressing the SUPERVISORY ACK key on the CP-3600(+). The SDACT(-2) will silence its
sounder and fully reset when the CP-3600(+) is reset either by pressing the RESET key or all self-
restoring supervisory alarms are restored and the SDACT(-2) has finished communicating to the central
station. A restore signal will be sent to the central station upon restoring the CP-3600(+) to normal
standby.
When a trouble is displayed by the CP-3600(+), the N.C. contacts on the trouble relay will open causing
a trouble transmission to be sent from Zone 4 on the SDACT(-2).
Note: A dialer fault trouble will not
activate the CP-3600(+) trouble relay.
Acknowledging the trouble on the CP-3600(+) will only silence
its internal sounder. The SDACT(-2) will silence its sounder and fully reset when the CP-3600(+) is
reset either by pressing the RESET key or all self-restoring troubles are restored. Note: Central station
notification of A/C loss in the CP-3600(+) and SDACT(-2) will be delayed by 120 minutes. If A/C is
restored prior to 120 minutes then no signal will be communicated to the central station. If A/C is
restored after the 120 minute delay then the CP-3600(+) and SDACT(-2) will restore to normal standby
automatically unless another trouble is pending. A restore signal will be sent to the central station upon
resetting the CP-3600(+) or self-restoration of an A/C loss. Note: Any trouble condition on the CP-
3600(+) will be sent with a Point I.D. of 3600.
If any trouble condition occurs as a result of a problem with the SDACT(-2) it will be annunciated on
the CP-3600(+) as a Dialer Fault. Refer to the Keltron SACT manual to determine the exact problem
with the dialer. The SDACT(-2) will communicate the trouble to the central station. Fixing the trouble
with the SDACT(-2) will automatically restore the dialer fault condition on the CP-3600(+). Note: A
trouble with the CP-3600(+) will also display a Dialer Fault however in this scenario the CP-3600(+)
trouble condition will also be displayed. The SDACT(-2) will only restore to normal when the CP-3600(+)
trouble condition is resolved. When the CP-3600(+) is put into test mode a TS (start test) and FT (fire
trouble) SIA code will be communicated to the central station. While in test mode Alarm, Supervisory,
Trouble or Point I.D.’s will not be communicated to the central station.