5.2.3 Notification Appliance Compatibility
The following UL Listed notification appliances are compatible with the CP-3600(+)
Control Panel
Table 1
MANUFACTURER
MODEL NUMBER
TYPE
MAX PER
NAC
CWSI 520(R)(W)
LOW
FREQ.
N/A
CWSI MH(R)(W)
MINI
HORN
N/A
GENTEX GX93-(W)(R)
MINI
HORN
20
GENTEX GEC-24-15/75-(WR)(WW)
HORN/STROBE 6
GENTEX GEC3-24-(WR)(WW)
HORN
STROBE
4
GENTEX GEC24-177-(WR)(WW)
HORN
STROBE 3
WHEELOCK HSR/HSW
HORN/STROBE
4
WHEELOCK DSM-12/24-R
SYNC
MODULE
1
SYSTEM SENSOR
P2R/P2W HORN/STROBE
4
SYSTEM SENSOR
MDL3R or MDL3W
SYNC MODULE
1
SYSTEM SENSOR
R-20E
RELAY
4*
CONTACT MANUFACTURER FOR COMPLETE PART NUMBERS AND OPTIONS.
REFER TO MANUFACTURER DOCUMENTATION FOR PROPER WIRING OF SYNC MODULES
* UP TO 4 RELAYS CAN BE CONNECTED WITHOUT ANY NOTIFICATION APPLIANCES CONNECTED OR
SUBSTITUTE 1 RELAY FOR 1 NOTIFICATION APPLIANCE IF USED TOGETHER. WHEN USING R-20E RELAYS
THEY SHOULD BE CONNECTED DIRECTLY TO THE NAC OUTPUTS BEFORE THE SYNC MODULE. DO NOT USE
THE R-20E ON A NAC WITH GENTEX SYNC OPTION ON.
Figure 6