P/N CWSI-IM-C3K6 Rev. F
© 2017 Johnson Controls. All rights reserved. All specifications and other information shown were current as of document revision
date and are subject to change without notice.
28
The Enter Old Password field will be highlighted and the blinking cursor will be under the first digit.
Enter the current password using the UP/DOWN and LEFT/RIGHT buttons. When the current password
is showing press the ENTER button and the Enter New Password field will now be highlighted. Enter
the new password and press the ENTER button to exit edit mode. Press the Cancel soft key to abort
the changes or the Save soft key to save the new password. You will be taken back to the Initial
Configuration Menu.
4.3.3 Base code Setup
The base code is the code that the enrolled devices use to know what CP-3600(+) they are reporting
to. When the CP-3600(+) is powered up it randomly chooses one of 252 random base codes to use. In
an installation where more than one CP-3600(+) is required, it is
mandatory
that the base codes be
different on each one so the devices will know which CP-3600(+) to report to. This is true where any
device, repeater or CP-3600(+) in one installation is in reception range of any device, repeater or CP-
3600(+) in the same or a different installation.
Warning: You must verify that each CP-3600(+) in
reception range of another has different base codes before enrolling any devices or repeaters.
If you change the base code after enrolling the devices then every enrolled device will have to
be deleted, have their base code cleared and then be enrolled again.
To look at the assigned base code and change it if necessary, highlight the Base code Setup menu
choice and press ENTER. The screen below will be shown.
To change the base code, press ENTER. The base code choices are 002 to 252. Base codes 000 and
001 are reserved for system use. Use the UP/DOWN buttons to choose the first digit in the code then
move the cursor to the second digit using the RIGHT button. Now enter the third digit the same way.
When the desired base code is displayed press the ENTER button to exit edit mode.
We strongly
recommend you do not change the base code unless absolutely necessary. Only change it
before enrolling any devices or repeaters. Changing it when devices, annunciators and
repeaters are enrolled will cause all enrolled devices, annunciators and repeaters to show test
failure.
When you are done making the desired changes press the Save soft key to save the change
and display the Initial Configuration Menu.
B a s e c o d e S e t u p
C a n c e l
B a s e c o d e : 0 2 7