4.8.2 Accessing the Audible Notification Device/Tandem Control Menu
Manual activation and deactivation of the audible notification devices and tandem smoke detectors can
be programmed under the AV Device/Tandem Controls program menu item. To access this menu press
the program soft key on the main system normal screen. Scroll down to AV Device/Tandem Controls
and press ENTER. The setup menu will now be displayed as shown below.
4.8.3 Programming Audible Notification/Tandem Device Manual
Activation and Deactivation
Move the cursor to the Device Type field and press enter. Use the down button and select either A/V
Device or Tandem Smoke Det. Selection and press enter. The Tandem CO Det choice is for future use.
The following description describes setting the Tandem Detector program settings. The same
programming options are available for the audible notification devices. The options for the audible
notification devices will affect those devices the same as described below for the tandem detectors.
Press the save soft key to go back to the main screen to program the on and off buttons as follows.
The default for Device On is “None”. This means the tandem detector sounders in the installation will
only be activated by zones. The Horns On button can be selected to activate all tandem sounders. To
program the Horns On button to activate ALL tandem detectors, move the cursor to the Device On field
and press ENTER. Use the UP/DOWN keys to select Horns On then press ENTER to exit edit mode.
Remember to save your changes.
The default for Device Off is “Reset”. This means the tandem detector sounders in the installation will
be reset when the RESET button is pressed. This also resets the CP-3600(+) control panel back to
normal. It may be desirable to reset ALL of the tandem detector sounders but leave the CP-3600(+) in
the alarm state. The Detector sounder silence button can be programmed for this function. It will silence
the tandem sounders but leave the CP-3600(+) showing alarms etc. To program the Detector sounder
silence button to silence the tandem sounders, move the cursor to the Device Off field and press
ENTER. Use the UP/DOWN keys to select Detector Sndr Silence then press ENTER to exit edit mode.
Remember to save your changes.
Note: The Horns On button when programmed to activate
audible notification devices (520/MH) will activate the temporal 3 pattern on those devices.
A V D e v i c e / T a n d e m D e t e c t o r s
C a n c e l
S e l e c t b u t t o n t o m a n u a l l y c o n t r o l a l l
A V D e v i c e / T a n d e m D e t e c t o r S o u n d e r s
D e v i c e T y p e : A / V D e v i c e
D e v i c e O n : H o r n s O n
D e v i c e O f f : R e s e t