P/N CWSI-IM-C3K6 Rev. F
© 2017 Johnson Controls. All rights reserved. All specifications and other information shown were current as of document revision
date and are subject to change without notice.
18
The screen below will be present on the LCD when a unit has been enrolled. The Devices Found
counter will increment as each unit is enrolled. There are also two sets of six digit numbers/letters
separated by a dash. These indicate the serial numbers of the unit being enrolled and the repeater it
has established communication with. The serial number to the left of the dash is the unit being enrolled
and the one to the right of the dash indicates the repeater it has established communication with.
If the number of enrolled devices exceeds the display limitation of one page on the LCD, page up and
page down soft keys will appear to allow the additional enrolled devices to be viewed.
It is highly
recommended that you write down the serial numbers of devices, annunciators and repeaters
as you enroll them so you can verify them against the LCD display to make sure all of them have
been enrolled.
The Devices Found count should also match the number of total units enrolled. After
the devices, annunciators and repeaters are enrolled they can be installed as outlined in the next
section. It is acceptable to enroll and install each device one by one rather than enrolling all the devices
then installing them. If you use this method, the CP-3600(+) has to remain in enrollment mode during
installation and the devices will have to be tested for alarm operation after enrollment and installation
of all the devices, annunciators and repeaters is completed.
3.4.2 Installing the Annunciators, Repeaters and Devices
Warning: All devices, annunciators and repeaters must be enrolled as described in the
previous
section prior to installing them.
This section assumes the devices, annunciators and repeaters have
already been enrolled to the CP-3600(+). After enrolling, the next step is to mount the devices,
annunciators and repeaters at their locations.
Important: As you install each device and repeater
make a list of their serial numbers along with a description of the mounting location. This
information is necessary so it can be entered into the description field for each device and
repeater.
During installation the CP-3600(+) can be placed in test mode or left in normal operation.
Placing the panel into test mode will abort any audible notification devices, NAC circuits or CP-3600(+)
alarm outputs from activating. Leaving the CP-3600(+) in normal operating mode will allow all alarm
functions to operate normally. The devices intended to directly communicate with the CP-3600(+)
should be installed first. Insert the battery in the device then hold the device at its desired position and
generate a signal survey transmission from it. Refer to the individual device manual and the signal
survey section of this manual for signal survey instructions. If the signal is acceptable the device may
be installed at that location. Slight transmitter location or orientation adjustments may have to be made
in order to obtain acceptable signal strength results. Do not mount any device unless acceptable signal
D e v i c e E n r o l l m e n t
L o o k i n g F o r D e v i c e s
D e v i c e s E n r o l l e d : 0 0 0 2
0 0 1 0 0 8 - 1 1 6 0 0 0
0 0 1 0 0 9 - 1 a 5 3 3 2
P o w e r u p d e v i c e t o b e e n r o l l e d
Serial # of the
unit being
enrolled
Serial # of the
repeater that the
enrolled unit is
communicating
with