2.2 Compatibility
The following UL Listed RF devices are compatible with the CP-3600(+) Control Panel:
CWSI Models:
A/C Repeater Model AR-5 Rev. 3.0, 3.1 – A/C powered repeater
WRA-3(R)(LG) – Remote Annunciator
SR-5 – Wireless Relay receiver
520(R)(W) Rev. 1.5 – Low Frequency Sounder (audible notification device) Compatible only with
Model AR-5 Rev. 3.1 repeater
MH(R)(W) Rev. 1.5 – Mini Horn Sounder (audible notification device) Compatible only with Model AR-
5 Rev. 3.1 repeater
Smoke Detector Model 300 – Photo Electric Smoke Detector with Integral Sounder
Smoke Detector Model 301 – Tandem Photo Electric Smoke Detector with Integral Sounder
Smoke Detector Model 302 – Photo Electric Smoke Detector without Sounder
Heat Detector Model 320 – 135° Heat Detector
Smoke Heat Detector Model 325 – Combination Smoke Heat Detector
Pull Station Model 310 – Manual Pull Station
Fire Transmitter Models 345(TS) – N.O. EOL Supervised Transmitter
CO Detector Model 350 – Carbon Monoxide Detector with Integral Sounder
The following antennas are for use with the CP-3600(+):
CWSI Models:
OM-1 Omni – Isotropic gain 2.5 dBi, OM-2 Omni – Isotropic gain 1 dBi, OM-3 Omni – Isotropic gain 5
dBi, YA-1 Yagi – Gain 15.2 dBi
The following UL Listed Digital communicators are compatible with the CP-3600(+) Control
Panel:
Silent Knight 5104B
Keltron SDACT, SDACT-2
The following accessories are for use with the CP-3600(+):
CWSI-BPF-915 Optional Band Pass Filter for Antenna SMA Connector
Notification Appliances:
As listed in the Notification Appliance Compatibility section of this manual.
Manual Service
Mount the pull station on a UL listed non-metallic junction box. Use a separate UL listed non-metallic
junction box with minimum inside dimensions of (HxWxD) 5” x 3” x 2” to house the model 345(TS)
transmitter. The two junction boxes shall be closed nippled together using a non-metallic conduit nipple.
Wire the transmitter to the pull station N.O. contacts. Refer to the 345(TS) manuals for wiring
instructions.