72
connected to the N.C. and C terminals of the trouble relay output of the SDACT(-2). There is no polarity
to this connection. This will allow any dialer trouble to be displayed on the CP-3600(+).
Figure 9
7.2.3 Programming
The programming instructions in this manual are intended to make the interface between the CP-
3600(+) and Keltron SDACT(-2) UL 864 compliant. You must program the SDACT(-2) with the
telephone number, account info etc. in order to report to the central station properly. Refer to the
SDACT(-2) manual for further information. Once the wiring and programming of the CP-3600(+) and
SDACT(-2) are complete, any alarms, supervisory or trouble conditions with either the CP-3600(+) or
the SDACT(-2) will be communicated off premises to a central station receiver. Only one programming
change will be required to allow the CP-3600(+) to be compatible with the SDACT(-2). Access the Dialer
Setup menu under the CP-3600(+) Setup screen. Turn the Keltron Dialer Enabled option to on and
save the setting. This will allow the CP-3600(+) to communicate through TB5 and activate monitoring
of the trouble input terminals. There are no software programming or jumper changes to make on the
Keltron SDACT(-2) for use in a fire alarm only installation. Use the default Event Codes and jumper
settings. If the CP-3600(+) is in an installation where Alarm level C is programmed for sprinkler
supervisory then use the Keltron SDACT(-2) software to change zone 3 Alarm Event to FS and the
Alarm Event Restore for zone 3 to FV.
7.2.4 Operation
The SDACT(-2) uses SIA codes to report to the central station. The CP-3600(+) will send the device
Point I.D. and applicable SIA codes to the SDACT(-2) serial port input. This information will also be
communicated to the central statjion by the SDACT(-2) as supplemental information. Table 4 shows
the CP-3600(+) events and the corresponding SIA codes that will be communicated.