TROUBLESHOOTING
RAS-
2
M
18
S3AV-A
1. Before Troubleshooting
Each model corresponds to DRED (Demand response enabling device) by AS/NZS 4755.3.1.
DRM1, DRM2 and DRM3 are executed as follows, upon directions from the power company,
Be sure to confirm they are not operated before usually troubleshooting.
Air conditioner demand response
*1: E30m = total electrical energy (kWh) used by the all conditioner for all purposes (including compressors,
controls and fans) over a 30 min period.
*2: R = rated input electrical power of the air conditioner (kW) at rated capacity in the mode in which it is
operating during the demand response event (i.e. cooling or heating).
2. Troubleshooting Procedure
When a symptom such as the following table is found without a check code is not displayed on the remote
controller, there is a possibility that a demand operation or demand P.C. board is failed, therefore diagnose it
according to the following diagram.
Demand response mode
DRM1
DRM2
DRM3
Description
Compressor off
E30m
≤
R × 0.50 × 0.5
E30m
≤
R × 0.75 × 0.5
Diagnosis when compressor does not work
Diagnosis when cooling/heating is poor
Disconnect the
connecting wiring
of DRED.
Remove wiring of
CN105 on DRED
P.C. board.
Disconnect the
connecting wiring
of DRED.
Normal
(Demand operation)
or DRED is failed.
Inverter Ass’y
is failed *1
Compressor works.
NO
YES
YES
YES
Demand
P.C. board is failed.
∗
Refer to next page
NO
NO
Normal
(Demand operation)
or DRED is failed.
Cooling/heating
improved.
NO
YES
Compressor works.
Indoor thermostat
is off.
Exchange of
Demand P.C. board
Abnormal cycle
system, etc. *1
NO
Indoor unit
satisfies ON conditions
of the compressor.
LED of the demand
P.C. board is on.
YES
When a failure with *1 appears,
advance the diagnosis further according
to the basic service manual.
1
Each condition is within the operating condition,
but the compressor does not work.
No.
Operating conditions of air conditioner
2
Cooling/Heating of the room is poor
- 9
2
-
FILE NO. SVM-15102