Item
Operation flow and applicable data, etc.
Description
2.
Outdoor fan
motor control
Heating operation
RAS-3M18S3AV-E, -TR
Compressor revolution (rps)
〜31
〜46
47〜
Outdoor temp. sensor To
Normal operation
To≧10℃
420
470
550
0≦To<10℃
470
550
700
-5≦To<0℃
700
700
730
To<-5℃
700
700
730
Sleep or quiet
To≧10℃
420*
420*
470*
operation
0≦To<10℃
470*
470*
550*
-5≦To<0℃
550*
550*
550*
To<-5℃
550*
550*
550*
To is abnormal
550
550
700
*Maximum revolution
To : Outdoor temp. sensor
RAS-2M18S3AV-E, -TR, -A
Compressor revolution (rps)
〜31
〜46
47〜
Outdoor temp. sensor To
Normal operation
To≧10℃
420
470
550
0≦To<10℃
470
550
680
-5≦To<0℃
680
680
730
To<-5℃
680
680
730
Sleep or quiet
To≧10℃
420*
420*
470*
operation
0≦To<10℃
470*
470*
550*
-5≦To<0℃
550*
550*
550*
To<-5℃
550*
550*
550*
To is abnormal
550
550
680
*Maximum revolution
To : Outdoor temp. sensor
RAS-2M14S3AV-E, -TR
Compressor revolution (rps)
〜31
〜46
47〜
Outdoor temp. sensor To
Normal operation
To≧10℃
420
470
550
0≦To<10℃
470
550
630
-5≦To<0℃
680
680
680
To<-5℃
680
680
680
Sleep or quiet
To≧10℃
420*
420*
470*
operation
0≦To<10℃
470*
470*
550*
-5≦To<0℃
550*
550*
550*
To<-5℃
550*
550*
550*
To is abnormal
550
550
630
Maximum revolution
*
To : Outdoor temp. sensor
Indoor unit A
Inverter
Outdoor unit
Compressor
Indoor unit B
Indoor unit C
3.
Capacity
control
1) Four indoor units from A to E determine the respective instruction revolutions from the difference
between the remote controller setting temperature (Ts) and the indoor temperature (Ta), and
transmit this to the outdoor unit.
2) The outdoor unit receives the instructions from the indoor units, and the inverter operates the
compressor at the calculated revolutions.
3) The compressor operation range in each operating mode is shown in the left table.
RAS-3M18S3AV-E, -TR
Operation
No.of
Compressor Operation
No.of
Compressor
mode
operating
revolution
mode
operating
revolution
unit
Combination
of indoor units
(kBTU)
(rps)
unit
Combination
of indoor units
(kBTU)
(rps)
COOL
1 unit
07
15〜46
HEAT
1 unit
07
15〜68
10
15〜46
10
15〜68
13
15〜70
13
15〜74
16
15〜78
16
15〜78
2 units
*
25〜83
2 units
*
25〜101
3 units
*
25〜86
3 units
*
25〜110
-
〜38
-
〜57
Sleep or quiet
operation
Sleep or quiet
operation
* In case that any multiple indoor units are combined.
FILE NO. SVM-15102
- 5