7-2.
Operation
Data
Outdoor
Unit
:
RAS-2M14S3AV-E, -TR
<Heating>
FILE NO. SVM-15102
- 4
3
-
Temperature
No.of
Standard
Compressor
condition
operating
pressure
Heat exchanger
pipe temperature
revolution
Indoor
Outdoor
units
A
B
C
P
(
MP
)
T1(
℃
)
T2(
℃
)
(
rps
)
1 unit
07
-
-
2.2 to 2.4 37 to 39
3 to 5
High
37
10
-
-
2.8 to 3.0 46 to 48
2 to 4
High
55
13
-
-
2.9 to 3.1 47 to 49
2 to 4
High
60
2 units
07
07
-
2.1 to 2.3 35 to 37
2 to 4
High
56
2
0/-
7/6
10
07
-
2.0 to 2.2 34 to 36
2 to 4
High
56
13
07
-
2.0 to 2.2 33 to 35
2 to 4
High
56
10
10
-
2.0 to 2.2 34 to 36
2 to 4
High
56
13
10
-
1.9 to 2.1 33 to 35
1 to 3
High
56
13
13
-
1.9 to 2.1 32 to 34
1 to 3
High
56
NOTES
:
1.Measure surface temperature of heat exchanger pipe around of heat exchanger path U bent.(Thermistor thermometer)
Connecting piping condition : 5 meters × 2 units(5m/each indoor unit)
2.
Indoor unit
Indoor
fan