7-2.
Operation
Data
Outdoor
Unit
:
RAS-2M14S3AV-E, -TR
<Cooling>
FILE NO. SVM-15102
- 4
2
-
Temperature
No.of
Standard
Compressor
condition
operating
pressure
Heat exchanger
pipe temperature
revolution
Indoor
Outdoor
units
A
B
C
P
(
MP
)
T1(
℃
)
T2(
℃
)
(
rps
)
1 unit
07
-
-
1.0 to 1.2 14 to 16
39 to 41
High
23
10
-
-
0.8 to 1.0 10 to 12
41 to 43
High
36
13
-
-
0.7 to 0.9
7 to 9
43 to 45
High
57
2 units
07
07
-
0.9 to 1.1 12 to 14
43 to 45
High
48
27/19
35/-
10
07
-
0.8 to 1.0 10 to 12
45 to 47
High
47
13
07
-
0.8 to 1.0 10 to 12
46 to 48
High
46
10
10
-
0.8 to 1.0 10 to 12
46 to 48
High
46
13
10
-
0.8 to 1.0 10 to 12
46 to 48
High
46
13
13
-
0.8 to 1.0 11 to 13
46 to 48
High
45
NOTES
:
1.Measure surface temperature of heat exchanger pipe around of heat exchanger path U bent.(Thermistor thermometer)
Connecting piping condition : 5 meters × 2 units(5m/each indoor unit)
2.
Indoor unit
Indoor
fan