7-2.
Operation
Data
Outdoor
Unit
:
RAS-3M18S3AV-E, -TR
<Heating>
Temperature
No.of
Standard
Heat exchanger
Compressor
condition
operating
pressure
pipe temperature
revolution
Indoor
Outdoor
units
A
B
C
P
(
MP
)
T1(
℃
)
T2(
℃
)
(
rps
)
1 unit
07
-
-
2.2 to 2.4 39 to 41
3 to 5
High
37
10
-
-
2.9 to 3.1 48 to 50
2 to 4
High
55
13
-
-
3.3 to 3.5 52 to 54
1 to 3
High
67
16
-
-
3.2 to 3.4 51 to 53
1 to 3
High
73
2 units
07
07
-
2.5 to 2.7 41 to 43
0 to 2
High
71
10
07
-
2.9 to 3.1 47 to 49
-1 to 1
High
90
13
07
-
2.8 to 3.0 45 to 47
-1 to 1
High
91
16
07
-
2.5 to 2.7 42 to 44
-1 to 1
High
91
10
10
-
2.8 to 3.0 46 to 48
-1 to 1
High
91
13
10
-
2.7 to 2.9 44 to 46
-1 to 1
High
91
16
10
-
2.4 to 2.6 41 to 43
-1 to 1
High
91
13
13
-
2.6 to 2.8 43 to 45
-1 to 1
High
91
2
0
/
-
7/6
16
13
-
2.3 to 2.5 39 to 41
-1 to 1
High
90
16
16
-
2.1 to 2.3 37 to 39
-1 to 1
High
90
3 units
07
07
07
2.1 to 2.3 36 to 38
-1 to 1
High
93
10
07
07
2.1 to 2.3 35 to 37
-1 to 1
High
93
13
07
07
2.0 to 2.2 35 to 37
-1 to 1
High
93
16
07
07
1.9 to 2.1 33 to 35
-1 to 1
High
93
10
10
07
2.0 to 2.2 35 to 37
-1 to 1
High
93
13
10
07
2.0 to 2.2 34 to 36
-1 to 1
High
93
16
10
07
1.9 to 2.1 33 to 35
-1 to 1
High
93
13
13
07
1.9 to 2.1 33 to 35
-1 to 1
High
93
16
13
07
1.9 to 2.1 32 to 34
-1 to 1
High
93
10
10
10
2.0 to 2.2 34 to 36
-1 to 1
High
93
13
10
10
2.0 to 2.2 34 to 36
-1 to 1
High
93
16
10
10
1.9 to 2.1 32 to 34
-1 to 1
High
93
13
13
10
1.9 to 2.1 33 to 35
-1 to 1
High
93
NOTES
:
1.Measure surface temperature of heat exchanger pipe around of heat exchanger path U bent.(Thermistor thermometer)
2.Connecting piping condition : 5 meters × 3 units(5m/each indoor unit)
Indoor unit
Indoor
fan
FILE NO. SVM-15102
-
39
-
Summary of Contents for RAS-2M14S3AV-E
Page 31: ...4 1 Outdoor Unit 4 CONSTRUCTION VIEWS FILE NO SVM 15102 31 Unit mm ...
Page 116: ......