5.4 Parameter instructions
In this section, the details of the setting parameters of each menu are explained.
Fig. 5.4.1 Basic setting
Refer to Table 5.3.1 for set range of each parameter.
[0-0] LCD Indication
0: Level
1: Distance
2: Volume
3: Flow
4: Current
5: Sig-Amp
6: Temperature
7: Max Volume
8: Max Flow
9: Volume Ratio
10: Flow Ratio
11: Elapsed Time from Start
12: Search Count Number of searches executed
13: Elapsed Time from Final Search
14: Margin of Sensitivity
[0-1] Measuring Unit
0: m
1: Ft
Note: When 'Measuring Unit' is changed, units of other parameters also change.
Reference point
Tank bottom
Zero level
R
C
H
G(+)
Output range
Gauging reference point