7-3
7.4 Setting volume calculation / flow calculation
(1) Volume calculation
To calculate volume, select a standard tank shape from among those in the "Volume calc. method"
setting parameter (vertical cylindrical shape / spherical shape / horizontal cylindrical shape) or
select a user definition. If you select a standard tank shape, set each of the required parameters.
The standard tank setting parameters are shown in the following table.
Table 7.4.1 Standard tank shape setting parameters
Setting parameter / tank shape
Vertical
cylinder shape
Sphere shape
Horizontal
cylinder shape
A (Maximum Position)
●
●
●
O (Tank offset)
●
●
●
D (Tank diameter)
●
●
●
L (Tank length)
-
-
●
If you select a user definition, you must set volume table.
Figure 7.4.1 Setting volume table
Volume table can be set using the configuration software. Between 2 (minimum) and 100
(maximum) calibration points can be set. If the size of the setting level values is wrong (not in
order of smallest [value]), an device status table error occurs, and functions will not operate. For
details on device status, refer to
5.4 Parameter instructions --> [8-3] Device Status
or
6.10
Tools --> Error
.