5-20
[8-2] Reboot
The device is rebooted.
0:
Default.
1: Reboot
Rebooted by "1" setting.
[8-3] Device Status
Error code will be shown on LCD. Detail meanings are as below.
Table. 5.4.2 Error code
Code Description
Possible
Cause
Counter-measure
E-00 Normal
-
-
E-01
ROM
(ROM Error)
ROM failure
Even if the transmitter
could not be recovered by
rebooting, please contact
your representative.
E-02
RAM
(RAM Error)
RAM failure
E-03
Transmitter
(Transmit/Receiving
circuit error)
Transmitter failure
E-04
Volume Table,
Flow Table
(Input parameter
error in the tables)
Inputted inconsistent data
in volume table or flow rate
Table, otherwise deviation
between Point number and
data
Check volume table or flow
rate table’s data.
E-05
Flow Calc. Method
(Flow rate
conversion error)
Out of limit for weir formula
Check weir construction
and input parameters.
Note: In case that multiple error detected, error code will be shown in following order.
E-01 > E-02 > E-03 > E-04 > E-05
[8-4] Firmware Version
Firmware version of the device will be shown LCD.
[8-5] HART Multidrop Mode
While this function is "On", HART multidrop mode is effective.
0: On
1: Off