10.
Area determination
5-15
5. Operations and
adjustment
TSC
10-1
Area determination
There are 2 types: "area determination" that sets the determination range by parameters and "P
area determination" that sets for STEP No. of the program table.
When the actuator enters into the range set by the parameter No.1 (Max. area)
(
→
P.5-19)
and
No.2 (Min. area)
(
→
P.5-19)
, AREA output (pin.26) is turned ON (, which is executable in function
modes 0, 4 and 5).
AREA output (pin.26) will also be output during job and inching operations.
When the actuator enters into the range configured in the "P area A (mm)" and "P area B (mm)"
of the "program table", the P AREA output (pin.27) turns ON (, which is executable in operation
modes 0, 1, 2, 4 and 5).
* The P area set for the running STEP No. is valid. The P area for other STEP No. is invalid.
For more information on settings, see the separate D-STEP or TDO Instruction Manual.
No.
Parameter name Set value
1
Max. area
100.00
2
Min. area
40.00
Area output signal "AREA"
P area output signal "P AREA"
80mm/s
30mm/s
STEP No.0
STEP No.1
50
60
90
110
100
40
Position
[mm]
Speed
STEP No.
ABS / INC
Position Speed
P area A
P area B
JUMP
Comment
[mm]
[mm/s]
[mm]
[mm]
[No.]
0
ABS
60.00
80
50.00
70.00
1
STEP No.0 operation (green)
1
ABS
120.00
30
90.00
110.00
E
STEP No.1 operation (blue)
* Some of the setting fields are omitted.