3. Wiring
3-2
TSC
Do not extend or shorten the pro-
vided cables.
Doing so may cause malfunctions or
impair the performance.
Be sure to perform single-point D-
type ground for the FG terminal of
this product.
Connect the grounding electrode
according to the laws, ordinances,
and regulations applied in respec-
tive regions and countries.
Fault or electric leakage may cause
electric shocks.
Do not ground the earth to the fol-
lowing locations:
Gas pipe…Explosion or fire may oc-
cur.
Conductor rod or telephone line…
It poses a danger in the event of
ground discharge.
Water line…It causes electric shocks.
In addition, the earth does not func-
tion if its middle section is made of
plastic.
Do not change the wiring or re-
move/insert the cables and con-
nectors while the devices are ener-
gized.
Doing so may cause abnormal opera-
tion, fault and electric shocks.
Do not
disassemble
Provide
grounding
connection
Do not damage, tuck, place a heavy
object on or apply excessive stress
on the cable.
Doing so may cause electric shocks.
Do not touch the energized parts
within TSC.
Doing so may cause electric shocks.
The wiring works must be per-
formed by electric work experts.
Failure to do so may cause electric
shocks.
Be careful to wire for the power
connectors properly.
Otherwise, fault, fire, or injury may re-
sult.
Perform wiring as described in this
manual.
Otherwise, you may be injured due to
malfunction.
The actuator cable is not a robot
cable.
Fix the cable before using it.
Caution –
Flammable
Obligatory
WARNING
1.
How to wire
Caution -
Electrical shock
Caution -
Electrical shock
When connecting TSC to the net-
work unit TNU, do not wire the CN5
pin number
①
(S1).
Doing so may cause fault.
CAUTION
Obligatory