10-9
LED display
Description
Cause
Possible solutions
bb6
(flash)
External
baseblock
External base block
(Terminal S6)
Multifunction digital input
external baseblock active.
Multi-function input
function set incorrectly.
Check wiring
OL1
Motor overload
Internal motor overload
protection tripped, active
when protection curve 08-05
= xxx1.
Voltage setting V/F mode
too high, resulting in
over-excitation of the motor.
Motor rated current (02-01)
set incorrectly.
Load too heavy.
Voltage setting V/F mode
too high, resulting in
over-excitation of the motor.
Inverter rating too small.
Load too heavy.
Check V/f curve.
Check motor rated current
Check and reduce motor
load, check and operation
duty cycle.
Check V/f curve.
Replace inverter with
larger rating.
Check and reduce motor
load, check and operation
duty cycle
OL2
Inverter overload
Inverter thermal overload
protection tripped.
If an inverter overload occurs
4 times in five minutes, it is
required to wait 4 minutes
before resetting the fault
CE
(flash)
communication
error
No Modbus communication
received for 2 sec.
Active when 09-07=3.
Connection lost or wire
broken.
Host stopped
communicating.
Check connection
Check host computer /
software.
CLB
over current
protection
level B
Inverter current reaches the
current protection level B.
Inverter current too high.
Load too heavy.
Check load and duty cycle
operation.
Retry
(flash)
retry
Automatic reset has
activated, and it displays
before the period of 07-01
automatic reset terminates.
The period of 07-01
automatic
reset≠0.
The times of 07-02
automatic
reset≠0.
It will disappear after the
period of automatic reset.
EF1
( flash )
External fault
(S1)
External fault (Terminal S1)
Active when 03-00= 25 or 68,
and Inverter external fault
selection 08-24=2.
Multifunction digital input
external fault active and
parameter 08-24 = 2 for
operation to continue.
Multi-function input
function set incorrectly.
Check wiring
Multi-function input
function set incorrectly.
Check wiring
EF2
(flash)
External fault
(S2)
External fault (Terminal S2)
Active when 03-01= 25 or 68,
and Inverter external fault
selection 08-24=2.
EF3
(flash)
External fault
(S3)
External fault (Terminal S3)
Active when 03-02= 25 or 68,
and Inverter external fault
selection 08-24=2.